Key points
- Turndown = Qmax ÷ Qmin at stated accuracy.
- Published turndown often assumes reference conditions (density, viscosity).
- Oversized meters spend most of their life near Qmin.
- Compare turndown on the same accuracy basis.
Published values compared
Values below come from Supmea product specifications; check the conditions behind each figure.
Worked sizing example
A cooling loop runs 12 m³/h normally, 4 m³/h at night and 18 m³/h at peak. A DN50 FLC420 covers 4–40 m³/h (10:1), so night flow sits exactly at the minimum. A DN40 covers 2–20 m³/h and keeps all three points inside the range, with normal flow mid-scale. Choose DN40 with reducers, and check pressure drop.
What reduces real turndown
- Density changes for vortex meters: the SUP-LUGB's 8:1 is stated at 1.2 kg/m³ gas and 1000 kg/m³ liquid.
- Viscosity for turbine meters: above 5×10⁻⁶ m²/s, calibrate on the actual liquid.
- Velocity limits for magmeters: below about 0.5 m/s the relative error grows.
- Installation: poor straight run hurts low-flow accuracy most. See magmeter installation.
Related questions
Is turndown the same as rangeability?
They are used interchangeably; both mean the ratio of maximum to minimum accurate flow.
Which technology has the highest turndown?
Thermal mass meters on gas and Coriolis meters typically offer very wide ranges; check the accuracy statement across the range.