FLC420 Turbine Flow Meter for Liquid Cooling

Short answer

The FLC420 is a turbine flow meter built for clean, low-viscosity liquids such as data center liquid-cooling coolant. It covers DN10 to DN200 (0.2 to 800 m³/h), with accuracy class 0.5 or 1.0, a 10:1 range ratio (6:1 at DN10), 250 ms response, active pulse output at 1–2000 Hz, and 12–24 VDC supply at 0.5 W or less. Threaded, flange and clamp connections are available.

Turbine flow meter line drawing0.00

What it does

Coolant loops in liquid-cooled racks often run deionised water or glycol mixtures whose conductivity is too low for a magnetic flow meter. A turbine meter measures velocity mechanically, so conductivity does not matter, and its pulse output responds quickly enough for pump control.

The FLC420 has no sealing ring in the flow body and draws very little power, which suits OEM CDU skids where many measuring points share a low-voltage supply.

Technical specifications

Nominal diameterDN10–DN200
Flow rangeDN10 0.2–1.2 m³/h … DN100 20–200 m³/h … DN200 80–800 m³/h
AccuracyClass 0.5 or 1.0
Repeatability⅓ of accuracy class
Range ratio1:10 (DN15–DN200); 1:6 (DN10)
Response time250 ms
OutputActive pulse, 1–2000 Hz (by size)
Power12–24 VDC; ≤0.15 W at 12 V, ≤0.5 W at 24 V
Medium viscosity<5×10⁻⁶ m²/s (calibrate with actual liquid above this)
Medium temperature−20 to 80 °C (stainless steel tube)
ConnectionsThreaded DN10–DN50 (PN<6.3 MPa); flange DN10–DN100 (PN<1.6 MPa); clamp; DN125–DN200 flange only
ElectricalAviation connector
Ambient−20 to 60 °C, 5–90% RH

Summarised from the official Supmea product page. The datasheet for your exact configuration governs. Ask us for it.

Key features

  • Works on low-conductivity coolant and DI water
  • No sealing ring in the flow body
  • Very low power for OEM skids
  • 250 ms response for pump control
  • Threaded, flange or clamp ends

Where it is used

Frequently asked questions

Why a turbine meter instead of a magmeter in a CDU?

TCS coolant is often below a magmeter's minimum conductivity; a turbine meter is unaffected by conductivity.

What output does the FLC420 provide?

An active pulse output, 1–2000 Hz depending on size, through an aviation connector.

Diagrams

How the turbine flow meter for liquid cooling works and how to install it.

Request the FLC420 datasheet and quotation

Send the medium, pipe size, flow or level range, temperature, pressure and required output. You'll get a recommended model, the datasheet and a quotation.

Tell us about the application

Fill in what you know. An application engineer replies with a model and datasheet, usually within one working day (Beijing time, UTC+8).

Both buttons open your own WhatsApp or email app with the message filled in. Nothing is stored on this website.