FLC420 Turbine Flow Meter for Liquid Cooling
The FLC420 is a turbine flow meter built for clean, low-viscosity liquids such as data center liquid-cooling coolant. It covers DN10 to DN200 (0.2 to 800 m³/h), with accuracy class 0.5 or 1.0, a 10:1 range ratio (6:1 at DN10), 250 ms response, active pulse output at 1–2000 Hz, and 12–24 VDC supply at 0.5 W or less. Threaded, flange and clamp connections are available.
What it does
Coolant loops in liquid-cooled racks often run deionised water or glycol mixtures whose conductivity is too low for a magnetic flow meter. A turbine meter measures velocity mechanically, so conductivity does not matter, and its pulse output responds quickly enough for pump control.
The FLC420 has no sealing ring in the flow body and draws very little power, which suits OEM CDU skids where many measuring points share a low-voltage supply.
Technical specifications
| Nominal diameter | DN10–DN200 |
|---|---|
| Flow range | DN10 0.2–1.2 m³/h … DN100 20–200 m³/h … DN200 80–800 m³/h |
| Accuracy | Class 0.5 or 1.0 |
| Repeatability | ⅓ of accuracy class |
| Range ratio | 1:10 (DN15–DN200); 1:6 (DN10) |
| Response time | 250 ms |
| Output | Active pulse, 1–2000 Hz (by size) |
| Power | 12–24 VDC; ≤0.15 W at 12 V, ≤0.5 W at 24 V |
| Medium viscosity | <5×10⁻⁶ m²/s (calibrate with actual liquid above this) |
| Medium temperature | −20 to 80 °C (stainless steel tube) |
| Connections | Threaded DN10–DN50 (PN<6.3 MPa); flange DN10–DN100 (PN<1.6 MPa); clamp; DN125–DN200 flange only |
| Electrical | Aviation connector |
| Ambient | −20 to 60 °C, 5–90% RH |
Summarised from the official Supmea product page. The datasheet for your exact configuration governs. Ask us for it.
Key features
- Works on low-conductivity coolant and DI water
- No sealing ring in the flow body
- Very low power for OEM skids
- 250 ms response for pump control
- Threaded, flange or clamp ends
Where it is used
- Data Center Liquid Cooling: CDU secondary (TCS) loop and rack manifold flow
- HVAC & District Energy: Small chilled-water and glycol branches
- Chemical Processing: Clean organic and inorganic liquids without fibres or particles
- Food & Beverage: Sanitary small-flow monitoring with clamp ends
Frequently asked questions
Why a turbine meter instead of a magmeter in a CDU?
TCS coolant is often below a magmeter's minimum conductivity; a turbine meter is unaffected by conductivity.
What output does the FLC420 provide?
An active pulse output, 1–2000 Hz depending on size, through an aviation connector.
Diagrams
How the turbine flow meter for liquid cooling works and how to install it.
Related questions
- How do you choose a flow meter for data center liquid cooling?Liquid cooling
Choose by loop and coolant. On the facility water side (FWS), a magnetic flow meter suits conductive chilled water in larger pipes. On the technology cooling side (TCS),…
- What sensors does a coolant distribution unit (CDU) need?Liquid cooling
A coolant distribution unit typically needs: secondary (TCS) flow; supply and return temperature on both the facility (FWS) and technology (TCS) sides; pump differential…
- What is turndown ratio in a flow meter, and why does it matter?Flow
Turndown ratio is the maximum flow divided by the minimum flow over which a meter stays within its stated accuracy. A meter rated 10:1 with a 100 m³/h maximum is…
Related instruments
Compact Pressure Transmitter
Small-format pressure for CDUs, pumps and chilled-water loops.
Programmable Temperature Transmitter
Turns RTD or thermocouple signals into a clean two-wire 4–20 mA loop.
Conductivity / TDS Controller
EC, TDS and resistivity from ultrapure water to 20 mS/cm.