SUP-2051 Differential Pressure Transmitter
The SUP-2051 is a single-crystal silicon differential pressure transmitter for measuring pressure difference, liquid level and flow (with an orifice or other primary element). It covers spans from about 1 kPa up to 3 MPa with ±0.075% accuracy, outputs 4–20 mA with HART, is IP67 rated, and has a 316L or Hastelloy C diaphragm. Static pressure error is ±0.05% per 10 MPa.
What it does
A dedicated DP transmitter measures a small difference on top of a high line pressure far more accurately than two separate gauge sensors. It is the standard instrument for filter and heat-exchanger ΔP, pump differential, orifice-plate flow and DP level in closed tanks.
Flange-mounted (SUP-2051LT) and dual-flange remote-seal (SUP-2051DP) versions handle viscous, hot or crystallising media for level.
Technical specifications
| Range | From ~1 kPa span up to 3 MPa (−100 kPa lower limit) |
|---|---|
| Accuracy | ±0.075% |
| Static pressure error | ±0.05% / 10 MPa |
| Output | 4–20 mA with HART |
| Power | 24 VDC |
| Medium temperature | −40 to 120 °C |
| Ambient temperature | −40 to 85 °C |
| Diaphragm | 316L, Hastelloy C, others on request |
| Housing | Aluminium alloy, epoxy coated |
| Protection | IP67 |
| Weight | 3.3 kg |
Summarised from the official Supmea product page. The datasheet for your exact configuration governs. Ask us for it.
Key features
- Single-crystal silicon sensing
- HART for remote configuration and diagnostics
- Low static-pressure effect
- Level and remote-seal variants (2051LT, 2051DP)
Where it is used
- HVAC & District Energy: Filter condition, coil ΔP and loop pump control
- Oil & Gas: Orifice-plate flow and separator level
- Chemical Processing: Closed-tank DP level with remote seals
- Data Center Liquid Cooling: CDU filter and heat-exchanger ΔP
Frequently asked questions
One DP transmitter or two gauge sensors?
For small ΔP at high static pressure, a DP transmitter. See our pressure types article for a worked example.
Can it measure flow?
Yes, with a primary element such as an orifice plate; flow is proportional to the square root of ΔP.
Diagrams
How the differential pressure transmitter works and how to install it.
Related questions
- Gauge vs absolute vs differential pressure transmitter: what is the difference?Pressure
A gauge pressure transmitter measures relative to local atmospheric pressure (0 when open to air). An absolute transmitter measures relative to a perfect vacuum, so it…
- 4–20 mA vs HART vs Modbus RTU: which output should you choose?Signals
Use 4–20 mA when you need one robust, universally accepted signal per instrument, especially over long cables or into safety systems. Add HART when you want remote…
Related instruments
Request the SUP-2051 datasheet and quotation
Send the medium, pipe size, flow or level range, temperature, pressure and required output. You'll get a recommended model, the datasheet and a quotation.
- WhatsApp +86 133 6211 7863
- geo@supmea.com
- +86 133 6211 7863
- Hangzhou Economic Development Area, Hangzhou 310018, Zhejiang, China