4–20 mA vs HART vs Modbus RTU: which output should you choose?

By Supmea Application EngineeringPublished Topic: Signals
Short answer

Use 4–20 mA when you need one robust, universally accepted signal per instrument, especially over long cables or into safety systems. Add HART when you want remote configuration and diagnostics on the same two wires. Choose Modbus RTU over RS-485 when many instruments share one controller and you want several values (flow, total, temperature, alarms) from each device with less wiring.

Key points

  • 4–20 mA: one value per pair of wires; 'live zero' at 4 mA reveals a broken loop.
  • HART: digital data superimposed on 4–20 mA; analog value stays the primary signal.
  • Modbus RTU: multi-drop digital bus; many values per device; needs addressing and termination.
  • Many Supmea instruments offer two at once, such as 4–20 mA plus RS485.

How each one works

4–20 mA represents 0–100% of range as a current, so cable resistance does not change the reading and a value below 4 mA signals a fault (current loop). HART superimposes a frequency-shift-keyed digital signal on the same loop, maintained by the FieldComm Group. Modbus RTU is a master/slave protocol, typically over two-wire RS-485, where each device has an address (Modbus Organization).

4–20 mA current loop with HART between transmitter and PLCTransmitterFT / PT / TT / ATPLC / DCS250 Ω input+ two-wire loop: power and signal on the same pairHART digital data rides on the same current (FSK)4 mA = 0 %20 mA = 100 %4–20 mA current loop
Figure 1. 4–20 mA current loop with HART between transmitter and PLC. Illustration: Supmea application engineering.

Comparison

Criterion4–20 mA4–20 mA + HARTModbus RTU (RS-485)
Values per device11 analog + several digitalMany
Wiring1 pair per device1 pair per device1 bus, daisy-chained
Loop-powered 2-wireYesYesUsually separate power
DiagnosticsFault current onlyYesYes (register map)
SpeedContinuousDigital part slow (~1200 bit/s)Polling, typically 9600–38400 bit/s
Typical usePLC/DCS inputs, SISProcess plants, asset managementSkids, CDUs, water SCADA, BMS gateways

Selection rules

  1. Safety or interlock signal: 4–20 mA (with HART if you want diagnostics).
  2. More than about 5 instruments on one skid controller: Modbus RTU reduces wiring and gives totals and alarms.
  3. Long cable runs in noisy plants: 4–20 mA, shielded twisted pair.
  4. Need both: many Supmea devices provide 4–20 mA and RS485 together, for example the LDG-SUP-A100 and SUP-TDS210-B.

Related questions

How many devices can share one RS-485 segment?

The RS-485 standard allows 32 unit loads per segment without repeaters; fewer if devices draw more than one unit load.

Does HART affect the 4–20 mA accuracy?

No. The HART signal averages to zero, so the analog value is unaffected.

Sources and further reading

Product specifications quoted here are summarised from Supmea datasheets. Confirm the figures for your exact model before final design.

Get a selection and quotation from an application engineer

Send the medium, pipe size, flow or level range, temperature, pressure and required output. You'll get a recommended model, the datasheet and a quotation.

Tell us about the application

Fill in what you know. An application engineer replies with a model and datasheet, usually within one working day (Beijing time, UTC+8).

Both buttons open your own WhatsApp or email app with the message filled in. Nothing is stored on this website.