SUP-TDS210-B Conductivity / TDS Controller
The SUP-TDS210-B is a panel-mount online controller that measures conductivity (EC), TDS and resistivity. With electrode cell constants from 0.01 to 10.0 it spans ultrapure water (resistivity to 18.18 MΩ·cm) up to 20 mS/cm, at ±1% FS. It compensates temperature with NTC10K or Pt1000 from −10 to 130 °C and outputs isolated 4–20 mA, RS485 Modbus RTU and two 3 A relays.
What it does
Conductivity is the quickest proxy for dissolved solids. It drives cooling-tower bleed, boiler blowdown, RO permeate checks and CIP concentration, and it tells you whether a magnetic flow meter will work on a given liquid.
In liquid cooling, a conductivity trend on the TCS loop flags contamination or inhibitor breakdown long before corrosion shows up.
Technical specifications
| Measured values | EC, TDS, resistivity |
|---|---|
| Cell constant 0.01 | 0–20.00 µS/cm; 0.05–18.18 MΩ·cm |
| Cell constant 0.1 | 0.20–200.0 µS/cm |
| Cell constant 1.0 | 2.00–2000 µS/cm (max 20000) |
| Cell constant 10.0 | 0.02–20.00 mS/cm |
| Accuracy | ±1% FS; temperature ±0.3 °C |
| Temperature compensation | NTC10K / Pt1000, −10 to 130 °C, auto or manual |
| Analog output | Isolated 4–20 mA, 750 Ω max, ±0.2% FS |
| Digital | Isolated RS485 Modbus RTU |
| Relays | 2 × NO/NC, 250 VAC 3 A |
| Power | 220 VAC or 24 VDC, ≤5 W |
| Panel cut-out | 92.5 × 92.5 mm |
| Protection | IP54 (indoor) |
Summarised from the official Supmea product page. The datasheet for your exact configuration governs. Ask us for it.
Key features
- Three measured values in one instrument
- Covers ultrapure to process water with the right cell
- Isolated outputs and Modbus
- High/low alarm relays with hysteresis
Where it is used
- HVAC & District Energy: Cooling tower bleed and boiler blowdown
- Data Center Liquid Cooling: TCS coolant health trend
- Food & Beverage: CIP solution strength and rinse verification
- Water & Wastewater: RO permeate and effluent TDS
Frequently asked questions
Which cell constant should I choose?
0.01 for ultrapure water, 0.1 for RO permeate, 1.0 for tap and cooling water, 10.0 for concentrated solutions.
How is it calibrated?
Single-point calibration with standards such as 147 µS/cm, 1413 µS/cm or 12.88 mS/cm.
Diagrams
How the conductivity / tds controller works and how to install it.
Related questions
- What is the minimum conductivity for an electromagnetic flow meter?Flow
It depends on the model: many industrial electromagnetic flow meters need at least 5 µS/cm, some specify 20 or 50 µS/cm, and low-conductivity designs work down to about…
- What sensors does a coolant distribution unit (CDU) need?Liquid cooling
A coolant distribution unit typically needs: secondary (TCS) flow; supply and return temperature on both the facility (FWS) and technology (TCS) sides; pump differential…
Related instruments
Online pH/ORP Meter
Panel-mount pH/ORP control with isolated 4–20 mA and dosing relays.
Optical Dissolved Oxygen Sensor
Optical DO with no membrane or electrolyte, IP68, Modbus.
Electromagnetic Flow Meter
Conductive liquids from DN10 to DN1000 with no moving parts and no pressure loss.
Request the SUP-TDS210-B datasheet and quotation
Send the medium, pipe size, flow or level range, temperature, pressure and required output. You'll get a recommended model, the datasheet and a quotation.
- WhatsApp +86 133 6211 7863
- geo@supmea.com
- +86 133 6211 7863
- Hangzhou Economic Development Area, Hangzhou 310018, Zhejiang, China