What sensors does a coolant distribution unit (CDU) need?

By Supmea Application EngineeringPublished Topic: Liquid cooling
Short answer

A coolant distribution unit typically needs: secondary (TCS) flow; supply and return temperature on both the facility (FWS) and technology (TCS) sides; pump differential pressure and filter ΔP; reservoir or expansion-tank level; and coolant quality, usually conductivity and pH. Together these give heat removed (flow × ΔT), pump and filter health, and early warning of leaks and coolant degradation.

Key points

  • Flow × ΔT gives heat removed; both must be accurate.
  • Pressure points show pump performance and filter loading.
  • Level trend plus pressure decay detect leaks.
  • Conductivity and pH trends detect contamination and inhibitor loss.

Measurement points

TagPointPurposeSupmea instrument
FT-1FWS flowFacility heat balanceLDG-SUP-A100
TT-2 / TT-4FWS and TCS supply/returnΔT, approach temperatureSUP-ST500 + Pt100
FT-3TCS flowRack flow, heat removedFLC420
PD-5Pump and filter ΔPPump health, filter loadingSUP-2051 or 2× SUP-PE100
LT-6Reservoir levelLeak detection, fill statusWSR201
AT-7Coolant conductivity / pHContamination, inhibitor depletionSUP-TDS210-B, SUP-PH6.5
Coolant distribution unit (CDU) with flow, temperature, pressure, level and analysis pointsCDUheat exchangerfiltertankFWS (facility water)TCS to racksFT1TT2FT3TT4PD5LT6AT7
Figure 1. Coolant distribution unit (CDU) with flow, temperature, pressure, level and analysis points. Illustration: Supmea application engineering.

How the signals are used

  • Capacity: Q = ṁ · cp · ΔT on the TCS side, cross-checked against the FWS side.
  • Control: pump speed on TCS differential pressure or flow; FWS valve on TCS supply temperature.
  • Alarms: low flow, high supply temperature, rising filter ΔP, falling reservoir level, conductivity step.

Design limits for supply temperature and water quality are covered in ASHRAE TC 9.9 data center resources and Open Compute Project work on liquid cooling.

Interfaces

CDU controllers usually take 4–20 mA, 0.5–4.5 V or Modbus RTU. Choosing instruments with Modbus reduces wiring when there are seven or more points; see 4–20 mA vs HART vs Modbus.

Related questions

Is a leak detection cable enough?

It detects liquid on the floor after the fact. Level trend and pressure decay can flag a slow leak earlier.

Why measure both FWS and TCS temperatures?

The approach temperature across the heat exchanger shows fouling and capacity margin.

Sources and further reading

Product specifications quoted here are summarised from Supmea datasheets. Confirm the figures for your exact model before final design.

Get a selection and quotation from an application engineer

Send the medium, pipe size, flow or level range, temperature, pressure and required output. You'll get a recommended model, the datasheet and a quotation.

Tell us about the application

Fill in what you know. An application engineer replies with a model and datasheet, usually within one working day (Beijing time, UTC+8).

Both buttons open your own WhatsApp or email app with the message filled in. Nothing is stored on this website.