Key points
- Flow × ΔT gives heat removed; both must be accurate.
- Pressure points show pump performance and filter loading.
- Level trend plus pressure decay detect leaks.
- Conductivity and pH trends detect contamination and inhibitor loss.
Measurement points
| Tag | Point | Purpose | Supmea instrument |
|---|---|---|---|
| FT-1 | FWS flow | Facility heat balance | LDG-SUP-A100 |
| TT-2 / TT-4 | FWS and TCS supply/return | ΔT, approach temperature | SUP-ST500 + Pt100 |
| FT-3 | TCS flow | Rack flow, heat removed | FLC420 |
| PD-5 | Pump and filter ΔP | Pump health, filter loading | SUP-2051 or 2× SUP-PE100 |
| LT-6 | Reservoir level | Leak detection, fill status | WSR201 |
| AT-7 | Coolant conductivity / pH | Contamination, inhibitor depletion | SUP-TDS210-B, SUP-PH6.5 |
How the signals are used
- Capacity: Q = ṁ · cp · ΔT on the TCS side, cross-checked against the FWS side.
- Control: pump speed on TCS differential pressure or flow; FWS valve on TCS supply temperature.
- Alarms: low flow, high supply temperature, rising filter ΔP, falling reservoir level, conductivity step.
Design limits for supply temperature and water quality are covered in ASHRAE TC 9.9 data center resources and Open Compute Project work on liquid cooling.
Interfaces
CDU controllers usually take 4–20 mA, 0.5–4.5 V or Modbus RTU. Choosing instruments with Modbus reduces wiring when there are seven or more points; see 4–20 mA vs HART vs Modbus.
Related questions
Is a leak detection cable enough?
It detects liquid on the floor after the fact. Level trend and pressure decay can flag a slow leak earlier.
Why measure both FWS and TCS temperatures?
The approach temperature across the heat exchanger shows fouling and capacity margin.